ICC 500-2020 Tested Above-Ground Steel Storm Shelters

Independently Tested at Intertek – Plano, Texas

Report No: Q9217.01-801-44-R0

100 MPH Missile Impact Testing



The shelter successfully received all required ICC 500 missile impacts without perforation.

• No penetration through doors, walls, or roof

• Vision panel resisted impact

• Deformation remained within ICC limits

The product met ICC 500-2020 impact requirements.

300 PSF Structural Pressure Testing



The shelter was subjected to positive and negative pressure testing up to 300 psf (200 psf design load).

Results:

• Structure remained intact

• Doors remained latched

• No structural failure

The shelter met ICC 500-2020 static pressure requirements.

Construction Details Tested



• 1/4” A36 steel plate walls and doors

• Fully welded vertical and horizontal connections

• Reinforced door perimeter

• Multi-point slide bolt latch system

• Deadbolt locking mechanism

• ICC-tested vision panel

For Distributors & Contractors

Testing conducted at Intertek Building & Construction Laboratory

Report No: Q9217.01-801-44-R0

Testing Date: January 29–30, 2024

Full documentation available upon request.