Above-ground shelter testing was conducted at Intertek in Plano, Texas.
Report No: Q9217.01-801-44-R0
Test specimen: 4 x 6-foot above-ground shelter.
Above-ground testing documents are available upon request. Confirm how the report applies to your selected size, configuration and local project requirements.
The shelter successfully received all required ICC 500 missile impacts without perforation.
• No penetration through doors, walls, or roof
• Vision panel resisted impact
• Deformation remained within ICC limits
The product met ICC 500-2020 impact requirements.

The shelter was subjected to positive and negative pressure testing up to 300 psf (200 psf design load).
Results:
• Structure remained intact
• Doors remained latched
• No structural failure
The shelter met ICC 500-2020 static pressure requirements.

• 1/4” A36 steel plate walls and doors
• Fully welded vertical and horizontal connections
• Reinforced door perimeter
• Multi-point slide bolt latch system
• Deadbolt locking mechanism
• ICC-tested vision panel

Testing conducted at Intertek Building & Construction Laboratory
Report No: Q9217.01-801-44-R0
Testing Date: January 29–30, 2024
Full documentation available upon request.